Description
PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
PR 4116 G3 Universal Transmitter Peters SL 1307 – PR Electronics
The PR Electronics 4116 G3 Universal Transmitter (Peters SL 1307) is a high-performance, FM-approved, and SIL 2-certified signal conditioning device designed for demanding industrial automation, process control, and safety applications. With universal input/output flexibility, robust isolation, and multiple relay options, the PR 4116 is one of the most versatile transmitters available for modern industries.
Key Features & Inputs
Universal input: RTD, thermocouple (TC), Ohm, potentiometer, mA, and V
Output: current, voltage, and two relays
2-wire supply > 16 V with signal isolation
Universal AC/DC power supply (21.6…253 VAC or 19.2…300 VDC)
FM-approved for Division 2 hazardous area installations
4-port 2.3 kVAC galvanic isolation for maximum safety
Applications
Temperature measurement with RTD and thermocouples (linearized, electronic).
Signal conversion: resistance variation to analog current/voltage for solenoids, butterfly valves, and potentiometers.
2-wire transmitter isolator and power supply for safe operations.
Process control with two potential-free relay contacts and analog outputs.
Galvanic separation and floating signal measurement.
Fully compliant with IEC 61508 / IEC 61511 (SIL 2) and ISO-13849 Performance Level “d”.
Safety, Certifications & Approvals
SIL 2 functional safety compliant for critical applications.
FM approval for Division 2 hazardous area use.
Certified by c UL us, UL 508, DNV Marine, EU RO MR.
Meets EMC (2014/30/EU), LVD (2014/35/EU), RoHS (2011/65/EU) compliance.
Designed with continuous self-diagnostics and failure monitoring.
Technical Performance
Accuracy: better than 0.1% of selected range.
Response time: ≤ 1 s (temperature input), ≤ 400 ms (mA/V input).
Signal dynamics: 24-bit input / 16-bit output.
Low power consumption – units can be mounted side-by-side, even at 60°C ambient temperature.
LED indicators (green/red/yellow) for operational status, malfunction, and relay activity.
Easy Programming & Installation
Configurable via PR 4500 detachable displays – no DIP-switch adjustments required.
Password-protected programming for secure configuration.
DIN rail mounting with compact size (109 x 23.5 x 104 mm).
Environmental Specifications
Operating temperature: -20°C to +60°C
Storage temperature: -20°C to +85°C
Protection degree: IP20
Vibration tested to IEC 60068-2-6 standards
Product Details
Part Number: PR 4116-G3
Manufacturer: PR Electronics
Origin: Denmark
Condition: New / Original Packing
Application
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 pairs of potential-free relay contacts and analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4116 provides the required failure data (SFF and PFDAVG) for SIL 2 applications as per IEC 61508 / IEC 61511.
- Failure rates for 4116 correspond to Performance Level “d” according to ISO-13849.
Technical characteristics – PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
- When 4116 is used in combination with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4116 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 4-port 2.3 kVAC galvanic isolation.
Mounting / installation / programming
- Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
- Configuration, monitoring, 2-point process calibration and more are accomplished using PR’s 4500 series of detachable displays.
- All programming can be password-protected.
If you have any other questions about 4116 Universal Transmitter / Temperature Transmitter, please contact us.
Data sheet & Manuals – PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications – 4116 G3 Universal transmitter Peters SL 1307
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
| Weight approx. | 175 g |
| Weight incl. 4501 / 451x (approx.) | 190 g / 205 g |
| Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
Common specifications – PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
Supply | |
| Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 2.5 W |
| Max. power dissipation | ≤ 2.5 W |
Isolation voltage | |
| Test voltage | 2.3 kVAC |
| Working voltage | 250 VAC (reinforced) / 500 VAC (basic) |
Response time | |
| Temperature input (0…90%, 100…10%) | ≤ 1 s |
| mA / V input (0…90%, 100…10%) | ≤ 400 ms |
Auxiliary supplies | |
| 2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
| Programming | PR 4500 communication interfaces |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Signal / noise ratio | Min. 60 dB (0…100 kHz) |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
RTD input | |
| RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
Linear resistance input | |
| Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer input | |
| Potentiometer min….max. | 10 Ω…100 kΩ |
TC input | |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input | |
| Measurement range | 0…23 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection: Loop break 4…20 mA | Yes |
Voltage input | |
| Measurement range | 0…12 VDC |
| Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
| Input resistance | Nom. 10 MΩ |
Output specifications – PR 4116 G3 Universal transmitter Peters SL 1307- PR Electronics
Current output | |
| Signal range | 0…23 mA |
| Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
| Load (@ current output) | ≤ 800 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Output limitation, on 4…20 and 20…4 mA signals | 3.8…20.5 mA |
| Output limitation, on 0…20 and 20…0 mA signals | 0…20.5 mA |
| Current limit | ≤ 28 mA |
Voltage output | |
| Signal range | 0…10 VDC |
| Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V |
| Load (@ voltage output) | ≥ 500 kΩ |
Relay output | |
| Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
| Max. voltage | 250 VAC / VDC |
| Max. current | 2 A |
| Max. AC power | 500 VA |
| Max. DC current, resistive load > 30 VDC | See manual for details |
Observed authority requirements
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| EAC | TR-CU 020/2011 |
| EAC LVD | TR-CU 004/2011 |
Approvals – PR 4116 G3 Universal transmitter Peters SL 1307 – PR Electronics
| c UL us, UL 508 | E231911 |
| FM | 3025177 |
| DNV Marine | TAA0000101 |
| EU RO MR Type Approval | MRA000000Z |
| SIL | Hardware assessed for use in SIL applications |