Description
PR 4114 Universal Transmitter – PR Electronics
The PR Electronics 4114 Universal Transmitter is a compact, FM-approved, and SIL-certified signal conditioning device designed for temperature measurement, resistance conversion, and process signal isolation. With universal input support and configurable current/voltage outputs, the PR 4114 delivers reliability, accuracy, and safety in demanding industrial environments.
Key Features
Universal input: RTD, TC, Ohm, potentiometer, mA, and V
Output: Configurable current and voltage ranges
2-wire supply > 16 V with signal isolator capability
Universal AC/DC supply (21.6…253 VAC or 19.2…300 VDC)
FM-approved for Division 2 hazardous area installation
3-port 2.3 kVAC galvanic isolation for maximum signal safety
Applications
Temperature measurement with RTD and thermocouple sensors
Signal conversion: resistance or potentiometer input to standard analog signals
Process control with accurate analog mA/V output
Signal isolator & power supply for 2-wire transmitters
SIL 2 installations requiring high safety standards
Performance Level “d” (ISO-13849) system applications
Advanced Functions
Configurable via PR 4500 detachable display
Process calibration, signal simulation, and error diagnostics
Password-protected programming with multilingual help text
Continuous integrity checks and front LED indicators (green/red for status)
Technical Highlights
Accuracy: Better than ±0.1% of selected range
Response time: ≤ 1 s (temperature), ≤ 400 ms (mA/V)
Wide input compatibility: Pt, Ni, Cu RTDs; multiple TC types (B, E, J, K, N, R, S, T, U, etc.); 0–23 mA; 0–12 VDC
Output flexibility: Programmable 0–20 mA, 4–20 mA, 0–10 VDC, and scaled voltage ranges
NAMUR NE43 compliant upscale/downscale error signaling
Compact DIN rail mount housing: 109 x 23.5 x 104 mm
Certifications & Approvals
FM 3025177 – Division 2 approval
c UL us, UL 508 (E231911)
DNV Marine TAA0000101
EU RO MR Type Approval MRA000000Z
RoHS, EMC, LVD, EAC compliance
Hardware assessed for SIL applications
Product Details
Part Number: PR 4114
Product Name: Universal Transmitter (mA/V output)
Manufacturer: PR Electronics
Origin: Denmark
Condition: New / Original Packing
PR Electronics – PR 4114 Universal Transmitter | mA/V output transmitter | Universal Temperature transmitter PR 4114 | PR Electronics signal isolator transmitter
Division 2 approved universal transmitter
PR Electronics SIL certified transmitter
RTD / TC universal signal transmitter
Industrial process control transmitter
DNV Marine approved universal transmitter
PR 4114 Universal Transmitter accepts universal input and gives mA/V output.
Advanced features
- Programmable by way of detachable display front (PR 4500 series), process calibration, signal simulation, password protection, error diagnostics and help text available in several languages.
Application – 4114 Universal Transmitter
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4114 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- When 4114 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4114 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
Data sheet PR 4114 – PR Electronics
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Weight approx. | 155 g |
| Weight incl. 4501 / 451x (approx.) | 170 g / 185 g |
| Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
Common specifications – PR 4114 Universal Transmitter
Supply | |
| Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 2.0 W |
| Max. power dissipation | ≤ 2.0 W |
Isolation voltage | |
| Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time | |
| Temperature input (0…90%, 100…10%) | ≤ 1 s |
| mA / V input (0…90%, 100…10%) | ≤ 400 ms |
Auxiliary supplies | |
| 2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
| Programming | PR 4500 communication interfaces |
| Signal / noise ratio | Min. 60 dB (0…100 kHz) |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 4114 Universal Transmitter
RTD input | |
| RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
Linear resistance input | |
| Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer input | |
| Potentiometer min….max. | 10 Ω…100 kΩ |
TC input | |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input – PR 4114 | |
| Measurement range | 0…23 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection: Loop break 4…20 mA | Yes |
Voltage input | |
| Measurement range | 0…12 VDC |
| Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
| Input resistance | Nom. 10 MΩ |
Output specifications – PR Electronics 4114 Universal Transmitter
Current output | |
| Signal range | 0…23 mA |
| Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
| Load (@ current output) | ≤ 800 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Output limitation, on 4…20 and 20…4 mA signals | 3.8…20.5 mA |
| Output limitation, on 0…20 and 20…0 mA signals | 0…20.5 mA |
| Current limit | ≤ 28 mA |
Voltage output | |
| Signal range | 0…10 VDC |
| Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V |
| Load (@ voltage output) | ≥ 500 kΩ |
| of span | = of the presently selected range |
Observed authority requirements
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| EAC | TR-CU 020/2011 |
| EAC LVD | TR-CU 004/2011 |
Approvals
| c UL us, UL 508 | E231911 |
| FM | 3025177 |
| DNV Marine | TAA0000101 |
| EU RO MR Type Approval | MRA000000Z |
| SIL | Hardware assessed for use in SIL applications |