Description
PR 4116 Universal Transmitter / Temperature Transmitter – PR Electronics
The PR Electronics 4116 Universal Transmitter / Temperature Transmitter is a versatile and high-performance signal conditioning device designed for demanding industrial automation and process control applications. With universal input options, galvanic isolation, and flexible output configurations, the PR 4116 is the preferred choice for engineers requiring accuracy, safety, and reliability.
Key Applications
Linearized electronic temperature measurement with RTD or thermocouple (TC) sensors.
Conversion of resistance variation into standard analog signals for solenoids, valves, and potentiometers.
Power supply and isolation for 2-wire transmitters.
Process control with two potential-free relay contacts and analog outputs.
Galvanic separation and safe measurement of floating signals.
Certified for SIL 2 installations and suitable for Performance Level “d” (ISO-13849) applications.
Technical Highlights
Universal input: RTD, TC, mA, V, resistance, potentiometer.
Universal power supply: 21.6…253 VAC / 19.2…300 VDC.
Fast response time: ≤ 1 s (temperature input), ≤ 400 ms (mA/V input).
High accuracy: Better than ±0.1% of selected range.
4-port 2.3 kVAC galvanic isolation for maximum safety.
LED indicators for status, relays, and diagnostics.
Continuous self-diagnostics and stored data monitoring.
Very low power consumption – units can be mounted side-by-side, even at 60°C ambient temperature.
Safety & Reliability
Built to strict international safety standards.
Certified for functional safety (SIL 2) applications.
EMC immunity according to NAMUR NE21.
Password-protected programming for secure operation.
Easy Setup & Programming
Compatible with PR 4500 detachable displays for configuration, monitoring, and calibration.
No need to open the device – electronic hardware switches replace traditional DIP-switches.
Quick installation on DIN rail with compact housing (109 x 23.5 x 104 mm).
Environmental Conditions
Operating temperature: -20°C to +60°C.
Storage temperature: -20°C to +85°C.
Protection degree: IP20.
Vibration tested (IEC 60068-2-6).
Product Benefits at a Glance
Universal, programmable transmitter with multi-input compatibility.
Cost-effective solution for industrial signal conditioning.
Compact, durable design suitable for harsh environments.
Enhanced safety for mission-critical process applications.
Backed by PR Electronics quality and reliability.
Applications
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current/voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 pairs of potential-free relay contacts and analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4116 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics of Universal Transmitter PR 4116
- When PR4116 Universal Transmitter / Temperature Transmitter is used in combination with the PR 4500 display series, all operational parameters can be modified to suit any application. As the PR4116 transmitter is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 4-port 2.3 kVAC galvanic isolation.
Mounting / installation / programming
- Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
- Configuration, monitoring, 2-point process calibration and more are accomplished using PR’s 4500 series of detachable displays.
- All programming can be password-protected for PR 4116 Universal Transmitter / Temperature Transmitter.
If you have any other questions about 4116 Universal Transmitter / Temperature Transmitter or the PR 4116 price, please contact us.
Environmental Conditions
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
Mechanical specifications – PR 4116 transmitter
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
| Weight approx. | 175 g |
| Weight incl. 4501 / 451x (approx.) | 190 g / 205 g |
| Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
Common specifications
Supply | |
| Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 2.5 W |
| Max. power dissipation | ≤ 2.5 W |
Isolation voltage | |
| Test voltage | 2.3 kVAC |
| Working voltage | 250 VAC (reinforced) / 500 VAC (basic) |
Response time – PR Universal Transmitter 4116 | |
| Temperature input (0…90%, 100…10%) | ≤ 1 s |
| mA / V input (0…90%, 100…10%) | ≤ 400 ms |
Auxiliary supplies | |
| 2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
| Programming | PR 4500 communication interfaces |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Signal / noise ratio | Min. 60 dB (0…100 kHz) |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input | |
| RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
| Short circuit detection | < 15 Ω |
Linear resistance input | |
| Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer input | |
| Potentiometer min….max. | 10 Ω…100 kΩ |
TC input | |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Sensor error detection | Yes |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input | |
| Measurement range | 0…23 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection: Loop break 4…20 mA | Yes |
Voltage input | |
| Measurement range | 0…12 VDC |
| Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
| Input resistance | Nom. 10 MΩ |