Description

Advanced features – 9113B EMP Temperature mA converter

  • Configuration and monitoring by way of detachable display front (PR 4500); process calibration and signal simulation.
  • Copying of the configuration from one device to others of the same type via the display front.
  • TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex, channel 2) for higher accuracy.
  • Advanced monitoring of internal communication and stored data.
  • SIL 2 functionality is optional and must be activated in a menu point.

Application

  • The device can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
  • Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
  • The 9113B-EMP has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics – 9113B EMP Temperature mA converter

  • 1 green and 2 red front LEDs indicate operation status and malfunction.
  • 2.6 kVAC galvanic isolation between input, output and supply.
  • Can be supplied separately or installed on power rail, PR type 9400.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Datasheet

Manual

Environmental Conditions – 9113B EMP Temperature mA converter

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500109 x 23.5 x 131 mm
Weight approx.250 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Stripping length5 mm
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage19.2…31.2 VDC
Fuse400 mA SB / 250 VAC
Max. required power≤ 0.8 W/≤ 1.4 W (1 ch./2 ch.)
Max. power dissipation, 1 / 2 ch.≤ 0.8 W / ≤ 1.4 W

Isolation voltage

Test /working: Input to any2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply1.5 kVAC / 150 VAC reinforced isolation

Response time

Temperature input, programmable (0…90%, 100…10%)1…60 s
mA / V input (programmable)0.4…60 s
ProgrammingPR 4500 communication interfaces
Signal / noise ratioMin. 60 dB (0…100 kHz)
Signal dynamics, input24 bit
Signal dynamics, output16 bit
AccuracyBetter than 0.1% of sel. range
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

RTD input

RTD typePt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire50 Ω (max.)
Sensor currentNom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionProgrammable ON / OFF

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 591020…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via int. mounted sensor±(2.0°C + 0.4°C * Δt)
Sensor error detectionProgrammable ON or OFF (only wire breakage)
Sensor error current: When detecting / elseNom. 2 μA / 0 μA

Current input

Measurement range0…23 mA
Programmable measurement ranges0…20 and 4…20 mA
Input resistanceNom. 20 Ω + PTC 50 Ω
Sensor error detectionProgrammable ON / OFF

Output specifications

Current output

Signal range0…23 mA
Programmable signal ranges0…20/4…20/20…0/20…4 mA
Load (@ current output)≤ 600 Ω
Load stability≤ 0.01% of span / 100 Ω
Sensor error indication0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale23 mA / 3.5 mA
Output limitation, on 4…20 and 20…4 mA signals3.8…20.5 mA
Output limitation, on 0…20 and 20…0 mA signals0…20.5 mA
Current limit≤ 28 mA

Passive 2-wire mA output

Max. external 2-wire supply26 VDC
Effect of external 2-wire supply voltage variation< 0.005% of span / V

Status relay

Max. voltage125 VAC / 110 VDC
Max. current0.5 AAC / 0.3 ADC
Max. AC power62.5 VA / 32 W

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
ATEX2014/34/EU & UK SI 2016/1107
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC ExTR-CU 012/2011
EAC LVDTR-CU 004/2011

Approvals – 9113B EMP Temperature mA converter

ATEXKEMA 07ATEX0148 X
IECExKEM 09.0052X
UKEXDEKRA 21UKEX0175X DEKRA 23UKEX0109X
c FM usFM19US0059X / FM19CA0032X
INMETRODEKRA 23.0005X
c UL us, UL 61010-1E314307
CCC2024322316005841
EAC ExEAEU KZ 7500361.01.01.08756
DNV MarineTAA00000JD
ClassNKTA24034M
SILSIL 2 certified & fully assessed acc. to IEC 61508

High-Precision Temperature Signal Conversion for Industrial Applications

The PR Electronics 9113B EMP Temperature mA Converter is a highly reliable and efficient signal conditioning device designed for precise temperature measurement in industrial environments. With superior galvanic isolation and flexible configuration options, the 9113B ensures accurate and stable signal transmission, making it ideal for process automation and monitoring applications.

Key Features – 9113B EMP Temperature mA converter

  • Universal Temperature Input – Supports RTD, thermocouple (TC), Ohm, and mV input signals for maximum versatility.
  • High-Accuracy mA Output – Provides precise 4-20 mA signal transmission, ensuring seamless integration with industrial control systems.
  • Advanced Galvanic Isolation – 2.6 kVAC isolation between input, output, and power supply, reducing interference and improving signal integrity.
  • Intrinsically Safe (Ex) Certified – 9113B EMP Temperature mA converter is approved for use in hazardous areas, enhancing operational safety.
  • Compact, DIN-Rail Mountable Design – Space-saving and easy to install for industrial applications.
  • Configurable via PC or PR 4501 – Enables quick and efficient parameter setup for optimized performance.

Applications:

The PR Electronics 9113B EMP Temperature mA Converter is widely used in industries that require precise temperature signal conversion, including:

  • Oil & Gas
  • Chemical and Pharmaceutical Manufacturing
  • Power Plants and Utilities
  • Industrial Automation and Process Control
  • HVAC and Energy Management Systems

Why Choose the PR Electronics 9113B?

With its high-precision temperature signal conversion, intrinsic safety certification, and advanced galvanic isolation, the 9113B EMP Temperature mA Converter is the perfect choice for professionals seeking accuracy and reliability in demanding industrial environments.

Upgrade Your Temperature Measurement System Today

Ensure stable and accurate temperature signal transmission with the PR Electronics 9113B EMP Temperature mA Converter. Contact us today for detailed specifications, pricing, and expert support.