Description
Advanced features – 9113B EMP Temperature mA converter
- Configuration and monitoring by way of detachable display front (PR 4500); process calibration and signal simulation.
- Copying of the configuration from one device to others of the same type via the display front.
- TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex, channel 2) for higher accuracy.
- Advanced monitoring of internal communication and stored data.
- SIL 2 functionality is optional and must be activated in a menu point.
Application
- The device can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
- Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
- The 9113B-EMP has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics – 9113B EMP Temperature mA converter
- 1 green and 2 red front LEDs indicate operation status and malfunction.
- 2.6 kVAC galvanic isolation between input, output and supply.
- Can be supplied separately or installed on power rail, PR type 9400.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Environmental Conditions – 9113B EMP Temperature mA converter
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20…28°C |
| Relative humidity | < 95% RH (non-cond.) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
| Weight approx. | 250 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
| Stripping length | 5 mm |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 |
| 2…13.2 Hz | ±1 mm |
| 13.2…100 Hz | ±0.7 g |
Common specifications
Supply | |
| Supply voltage | 19.2…31.2 VDC |
| Fuse | 400 mA SB / 250 VAC |
| Max. required power | ≤ 0.8 W/≤ 1.4 W (1 ch./2 ch.) |
| Max. power dissipation, 1 / 2 ch. | ≤ 0.8 W / ≤ 1.4 W |
Isolation voltage | |
| Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
| Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time | |
| Temperature input, programmable (0…90%, 100…10%) | 1…60 s |
| mA / V input (programmable) | 0.4…60 s |
| Programming | PR 4500 communication interfaces |
| Signal / noise ratio | Min. 60 dB (0…100 kHz) |
| Signal dynamics, input | 24 bit |
| Signal dynamics, output | 16 bit |
| Accuracy | Better than 0.1% of sel. range |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input | |
| RTD type | Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 50 Ω (max.) |
| Sensor current | Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Programmable ON / OFF |
TC input | |
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
| CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
| Sensor error detection | Programmable ON or OFF (only wire breakage) |
| Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input | |
| Measurement range | 0…23 mA |
| Programmable measurement ranges | 0…20 and 4…20 mA |
| Input resistance | Nom. 20 Ω + PTC 50 Ω |
| Sensor error detection | Programmable ON / OFF |
Output specifications
Current output | |
| Signal range | 0…23 mA |
| Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | 0 / 3.5 / 23 mA / none |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
| Output limitation, on 4…20 and 20…4 mA signals | 3.8…20.5 mA |
| Output limitation, on 0…20 and 20…0 mA signals | 0…20.5 mA |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output | |
| Max. external 2-wire supply | 26 VDC |
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Status relay | |
| Max. voltage | 125 VAC / 110 VDC |
| Max. current | 0.5 AAC / 0.3 ADC |
| Max. AC power | 62.5 VA / 32 W |
Observed authority requirements
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| ATEX | 2014/34/EU & UK SI 2016/1107 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| EAC | TR-CU 020/2011 |
| EAC Ex | TR-CU 012/2011 |
| EAC LVD | TR-CU 004/2011 |
Approvals – 9113B EMP Temperature mA converter
| ATEX | KEMA 07ATEX0148 X |
| IECEx | KEM 09.0052X |
| UKEX | DEKRA 21UKEX0175X DEKRA 23UKEX0109X |
| c FM us | FM19US0059X / FM19CA0032X |
| INMETRO | DEKRA 23.0005X |
| c UL us, UL 61010-1 | E314307 |
| CCC | 2024322316005841 |
| EAC Ex | EAEU KZ 7500361.01.01.08756 |
| DNV Marine | TAA00000JD |
| ClassNK | TA24034M |
| SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |
High-Precision Temperature Signal Conversion for Industrial Applications
The PR Electronics 9113B EMP Temperature mA Converter is a highly reliable and efficient signal conditioning device designed for precise temperature measurement in industrial environments. With superior galvanic isolation and flexible configuration options, the 9113B ensures accurate and stable signal transmission, making it ideal for process automation and monitoring applications.
Key Features – 9113B EMP Temperature mA converter
- Universal Temperature Input – Supports RTD, thermocouple (TC), Ohm, and mV input signals for maximum versatility.
- High-Accuracy mA Output – Provides precise 4-20 mA signal transmission, ensuring seamless integration with industrial control systems.
- Advanced Galvanic Isolation – 2.6 kVAC isolation between input, output, and power supply, reducing interference and improving signal integrity.
- Intrinsically Safe (Ex) Certified – 9113B EMP Temperature mA converter is approved for use in hazardous areas, enhancing operational safety.
- Compact, DIN-Rail Mountable Design – Space-saving and easy to install for industrial applications.
- Configurable via PC or PR 4501 – Enables quick and efficient parameter setup for optimized performance.
Applications:
The PR Electronics 9113B EMP Temperature mA Converter is widely used in industries that require precise temperature signal conversion, including:
- Oil & Gas
- Chemical and Pharmaceutical Manufacturing
- Power Plants and Utilities
- Industrial Automation and Process Control
- HVAC and Energy Management Systems
Why Choose the PR Electronics 9113B?
With its high-precision temperature signal conversion, intrinsic safety certification, and advanced galvanic isolation, the 9113B EMP Temperature mA Converter is the perfect choice for professionals seeking accuracy and reliability in demanding industrial environments.
Upgrade Your Temperature Measurement System Today
Ensure stable and accurate temperature signal transmission with the PR Electronics 9113B EMP Temperature mA Converter. Contact us today for detailed specifications, pricing, and expert support.